Switch Services Commands
Use these commands to configure switch services.
This section describes the switch services commands. Switch services are services that provide support for features such as temperature, power supply status, fan control, and others. Each of these services is platform dependent. (For example, some platforms may have temperature sensors, but no fan controller. Or, others may have both while others have neither.)
environment fan control mode
M4250
M4350
Use this command to set the fan mode.
| Format | environment fan control mode {auto | cool | off | quiet} |
| Mode | Global Config |
| Parameter | Definition |
|---|---|
| auto | Sets the fans to Auto mode, which, in this firmware version, is identical to quiet mode. |
| cool |
Sets the fans to Cool mode. In Cool mode, the fans consistently function at 100 percent speed, provide maximum cooling, and produce considerable noise.
Note: In Quiet mode, the switch might automatically change back and forth between Cool mode and Quiet mode until a temperature, PoE budget, or traffic load condition returns within thresholds.
|
| off |
Sets the fans to Off mode. In Off mode, the fans produce no noise. You can only manually set the fans in Off mode. Off mode is not supported on some models. |
| quiet |
Sets the fans to Quiet mode, which is the default mode. In Quiet mode, the following applies:
Note: For detailed information about temperature thresholds, PoE budgets, and traffic load conditions that affect the fans, see the hardware installation guide, which you can download by visiting netgear.com/support/enterprise.
|
environment temprange
M4250
M4350
Use this command to set the allowed temperature range for normal operation.
| Format | environment temprange min temperature max temperature |
| Mode | Global Config |
| Parameter | Definition |
|---|---|
| min temperature | Sets the minimum allowed temperature for normal operation. The range is between –100°C and 100°C. The default is 0°C. |
| max temperature | Sets the maximum allowed temperature for normal operation. The range is between –100°C and 100°C. The default is 0°C. |
environment trap
M4250
M4350
Use this command to configure environment status traps.
| Format | environment trap {fan | powersupply | temperature} |
| Mode | Global Config |
| Parameter | Definition |
|---|---|
| fan | Enables or disables the sending of traps for fan status events. The default is enable. |
| powersupply | Enables or disables the sending of traps for power supply status events. The default is enable. |
| temperature | Enables or disables the sending of traps for temperature status events. The default is enable. |